Product Description
  • Types HQP, QPHW, QHPX, QHPW
  • Built and listed to UL 489
  • All products UL and CSA listed
  • All products 15 – 100A are HACR rated
  • Switching duty rated for 120V AC fluorescent light applications

QUICKLAG Bolt-On

Product Description
  • Types BAB, QBHW, HBAX, HBAW
  • Built and listed to UL 489
  • All products UL and CSA listed
  • All products 15 – 100A are HACR rated
  • Switching duty rated for 120V AC fluorescent light applications
  • Dimension Sheets — FRED Index 206

QUICKLAG Cable-In/Cable-Out

Product Description

  • Types QC, QCHW, QHCX, QHCW
  • Built and listed to UL 489
  • All products UL and CSA listed
  • All products 10 – 100A are HACR rated
  • Switching duty rated for 120V AC fluorescent light applications only

QUICKLAG 1/2" Wide Breakers

Types QCR, QCF, QCRH, QCFH circuit breakers are only 1/2-inch (12.7 mm) wide per pole and are excellent for general purpose industrial applications where space savings is required.

Type QCR have as a standard feature provisions for 35 mm DIN rail rear mounting with a spring-loaded release. Optional clips for individual mounting are available as a separate accessory.

Type QCF have two threaded steel inserts to facilitate front mounting with #6 – 32 steel screws. The clamp type terminals are accessible from the rear of the breaker so that cables can be accessed without removal of the breaker from the front cover.

Features, Benefits and Functions
  • 1/2-inch (12.7 mm) wide per pole
  • Cable-in/cable-out
  • Black cases with black handles
  • Three position handle: ON, Tripped (center), OFF
  • Thermal-magnetic protection
  • One-, two- and three-pole
  • 10 kAIC at 120/240V AC, 10 – 60 amperes
  • 22 kAIC at 120/240V AC, 15 – 20 amperes
  • 10 kAIC at 240V AC, 10 – 30 amperes
  • 3 kAIC at 62.5V DC (1-pole)
  • 3 kAIC at 130V DC (2 poles in series)
  • Normal operating environment: 0 – 40?C 5 – 95% humidity (non-condensating)
Standards and Certifications
  • Built and Listed to UL 489
  • UL File E7819
  • CSA File LR48907
  • Type QCR and QCF circuit breakers are UL listed circuit breakers that are suitable for use as branch circuit protectors
  • All ratings 15 – 60A are HACR rated

Solenoid-Operated, Remote-Controlled

Types GHBS, GBHS and BABR circuit breakers are bolt-on branch circuit breakers designed for use in panelboards and are ideally suited for lighting control applications. In addition to providing conventional branch circuit protection, they include a unique solenoid-operated mechanism that provides for efficient breaker pulse-on and pulse-off operation when used with a suitable controller like Eaton Pow-R-Command lighting control system. The BABR can also be controlled by pushbutton or a PLC unit.

Features, Benefits and Functions
  • Bolt-on line-side terminal
  • Cable connected load-side terminal
  • 3- or 4-prong control terminal for GHBS or BABR respectively
  • Bi-metal assembly for thermal over-load protection
  • Fast acting short circuit protection
  • Arc-runner and arc-chute assembly for fast acting arc extinction
  • Three-position handle: OFF, TRIP (Center), ON
  • Manual switching is permitted when control power is lost
  • Mechanical trip indicator
  • 15 and 20 ampere breakers SWD (Switching Duty) rated
  • HID ratings for HID (High Intensity Discharge) lighting
  • All models are HACR rated
  • Status feedback of control circuit
Operation

The remote-control capability of the breaker is "armed" when the breaker handle is manually switched to the ON position. Once armed, the breaker can be pulsed ON and OFF by a controller device which provides an AC pulse of specified magnitude and duration to the solenoid-operated mechanism. Control connections to the GHBS breaker are provided through a male conductor plug (purchased separately) which snaps into the female connector provided with the breaker.

Operating Data
  • Ambient temperature: 0 – 40? C
  • Nominal pulse magnitude: GHBS – 28V AC, BABR – 24V AC
  • Tolerance: +10% to -15% of nominal voltage
  • Maximum breaker cycling: 6 operations per minute
  • Humidity: 0 – 95% non-condensing
E-mail this page Print this page